Frequently Asked Questions
The following are answers to some of the frequently asked questions:
- Up/down temperature
variation in two-story house
- Side-to-side
temperature variation as the sun moves around
- Can I use one fan cycler controller
for two air handlers?
- I have two air handlers, do I
need an outside air duct to both?
- Will outside humidity be a problem?
- Will cold outside air be a problem?
- Fan cycling without damper
cycling
- How much can I expect to pay for
electricity to operate?
- What about an ERV?
-
Central-fan-integrated supply ventilation with damper cycling but not
fan cycling
- Big house with multiple air handlers
- Outside air estimate with a
Central Fan Integrated Supply
- I am wondering what risk there is
for mold in the ducts using the CFIS system?
- Make-up air for exhaust devices?
Q. I have a two story house with the
heating and cooling thermostat on the first level. The temperature in
upstairs rooms is inconsistent with the downstairs and we not
comfortable throughout the house. Can the FanCycler® help me with that
problem?
A. Yes. The FanCycler will periodically
operate the central system fan to re-average the indoor environmental
conditions (temperature, humidity, air quality) throughout the zone it
serves. In your case, that means that the upstairs air will mix with the
downstairs air to smooth out variations and give the thermostat better
feedback on the true average temperature of the house. The same holds
true for single story houses with open or closed rooms that are not near
the thermostat.
If you are still unsure, a good test you can try is to turn your
central blower from AUTO to ON for awhile. If you are satisfied with
continuous blower operation after a day or two, then the FanCycler will
give you the same performance at reduced operating cost. You can adjust
the FanCycler settings to optimize for your situation (i.e. find the
best Fan OFF and Fan ON times for you).
Q. Some rooms in our house can be very
uncomfortable depending on where the sun is, can the FanCycler solve
that problem?
A. In most cases, yes. Similar to the
question above, the FanCycler will smooth out temperature variations
from room to room by periodically mixing air from all parts of the
house. The FanCycler’s patented fan recycling strategy operates the
central blower if it has been inactive for a period of time. This is
effective in making rooms throughout the house more comfortable whether
the discomfort be due to variations in solar heat gains as a function of
time-of-day, or due to door closure, distance from the thermostat,
inadequate insulation, or poor duct design. Of course, there are
limitations, if the insulation is severely inadequate, or worse, the
duct design doesn’t allow much air flow to the uncomfortable space, then
the effectiveness will be diminished.
Q. My house has two central air
handlers. Do I need to use two FanCyclers or can I make one FanCycler
operate both systems?
A. If you want fan recycling capability
on both units, then you need two FanCyclers. The control wiring for each
air handler unit needs to be isolated from the other.
Q. I am using central-fan-integrated
ventilation with the FanCycler for my house that has two air handlers.
Should I install an outside air duct to the return of both systems or
just one?
A. It would be best to install a smaller
outside air duct to the return of both air handlers. Splitting the
heating and cooling load for ventilation air between the two systems
will give better performance and will give better distribution of
ventilation air throughout the house. If you have to choose only one
system, choose the one that serves the bedrooms since that is where
people will be for the longest time.
Q. I live in a humid cooling dominated
climate. My HVAC contractor tells me that drawing fresh air to the
return side off my cooling system blower will be too hard on my cooling
system. Is that true?
A. No, as long as the following is true.
The air distribution system (blower and ducts) should either be inside
the conditioned space or they should be well sealed with mastic or foil
tape so that the air leakage from the ducts to outside is less than 5%
of the air handler flow rate. The house should also be constructed to
reduce the random and unknown quantity of air leakage from outdoors,
while allowing the mechanical ventilation system to provide and
distribute a known amount of fresh air, from a known source, on a
regular basis.
Q. I
live in a cold climate. My heating equipment supplier has raised a
concern about cold outside air affecting my gas furnace. Can you comment
on that?
A. Furnace manufacturers put a lower
limit on the return air temperature that their gas furnaces are exposed
to. Based on a survey of manufacturers, summarized in Table 1, the lower
limit is between 50oF and 55oF for intermittent operation and 60oF for
continuous blower operation. This means that when cold outside air is
mixed with recirculated house air, the resulting mixed return air
temperature should not be less than the minimum specified by the furnace
manufacturer. The mixed return air temperature is calculated as the
fraction of outside air times the outside air temperature plus the
fraction of inside air times the inside air temperature. Figure 1 shows
the results of that calculation for a range of outside air temperatures
and outside air fractions. Referring to Figure 1, for an outside air
fraction of 15% and an outside air temperature of -30oF the mixed return
air temperature is 55oF. From that, you can see that the outdoor
temperature conditions have to be pretty severe before this becomes a
concern. I recommend outside air fractions as shown in Table 2.
Table 1. Summary of survey of furnace manufacturers regarding
minimum return air temperature
|
Manufacturer |
Minimum return air temperature (oF) |
Other brands included |
|
Any operation |
Intermittent operation |
Continuous operation |
| Trane |
55 |
|
|
American Standard |
| Carrier |
|
55 |
60 |
Bryant |
| ICP |
|
55 |
|
Tempstar, Heil, Comfortmaker, Arcoaire, KeepRite |
| Johnson Controls |
55 |
|
|
York, Coleman |
| Lennox |
|
55 |
60 |
|
| Nordyne |
50 |
|
|
Westinghouse, Tappan, Kelvinator, Grandaire, Frigidaire,
Philco, Gibson, Intertherm, Miller, Maytag |
| Rheem |
55 |
|
|
|

Figure 1. Mixed return air temperature for a range of outside air
temperatures and outside air fractions.
Table 2. Recommended outside air fractions by climate.
|
International
Energy Conservation Code (IECC) Climate Zone |
Description |
Maximum outside
air fraction |
|
1, 2, 3, 4 |
Hot-humid, hot-dry,
mixed-humid, mixed-dry |
15% |
|
5, 6, 7 |
Cold |
10% |
|
8 |
Very cold
|
5% |
Q. Under what circumstances would fan
cycling be used without motorized damper cycling?
A. Fan cycling without motorized damper
cycling would be used in the following cases:
- Builders who use central-fan-integrated supply ventilation but
have to get off the ground with the basic system before they can sell
or absorb the cost of upgrading to the motorized damper. The motorized
outside air damper and associated cycling control eliminates
over-ventilation during long heating or cooling cycles and closes the
connection to outdoors when the fan is off. In our Building America
program, the priority for getting builders to upgrade started in 2001,
beginning with the hot-humid climate. The severe-cold climate would be
in the same category, then hot-dry, cold, mixed-humid, and mixed-dry.
- Builders who use fan cycling only as a mixing tool to distribute
ventilation air and provide whole-house mixing for comfort and indoor
air quality. In that case, they would likely be bringing in outside
air by either a separate supply fan, an exhaust fan, or a HRV/ERV that
was not fully ducted to provide air distribution throughout the house.
Q. How
much can I expect to pay for electricity to operate my central fan with
the fan cycler controls for ventilation and whole-house mixing?
A. As a reality check, based on my
monitoring in many U.S. climate regions, it has mostly worked out to
about half the year needing fan cycling. At 33% duty cycle, that means
that the fan operation charged to ventilation and whole-house mixing
would be about 15% to 20% of the total hours in year (0.5/3=0.17).
That's about 1500 hours per year, which, for a 500 W fan, is 750 kWh/yr,
or $75/yr at $0.10/kWh. If an electronically commutated motor (ECM) is
used with the blower instead of the more common permanent split
capacitor motor, 1/2 to 2/3 less energy consumption can be expected.
Results came out in the same range in a 2001 study conducted by the
National Association of Home Builders Research Center, entitled, "Field
Investigation of Mechanical Ventilation Strategies in Residential
Construction," prepared for the U.S. Environmental Protection Agency.
Q. I have a new home in Waco, Texas. I
am in search of an Energy Recovery Ventilator (ERV) to install that will
have a reasonable acquisition cost and service life. Can you send me
some guidance?
A. There are no inexpensive ERV's that I
know of--mostly in the range of $750 contractor price to $1200 retail
price. Unless you need a lot of outside air (more than ASHRAE Standard
62.2 requires), the energy savings of an ERV will not pay for the more
costly equipment for a long time (10+ years). Neither will an ERV
provide year-around humidity control because it cannot dehumidify house
air, it can only lessen the incoming load. You also have to consider the
cost of ducting to get distribution of the ventilation air (at least $75
for each intake or outlet in new construction). If you still want an ERV,
there are number of fine units on the market. Venmar makes good units,
and Shelter Supply in Minnesota is one good place to buy them.
I would recommend a less expensive but very effective and practical
system for you. We call it central-fan-integrated supply ventilation. It
involves a 6" outside air duct connected to the return side of your air
handling unit with a controller that makes sure the fan operates enough
if it already hasn't, and makes sure that a damper closes off the
outside air if the fan operates longer than needed. For more
information, see the Products
page.
If you want to control humidity year-around, even when it is not hot
outside and the thermostat is not calling for cooling, you should add a
dehumidifier separate from your cooling system. You can see a number of
successful configurations by exploring www.buildingscience.com.
Aprilaire sells an Energy Star® dehumidifier package (model 1700) with
the ventilation controller already built in. It should cost about $1000
for the equipment including a motorized outside air damper, which is no
more than the ERV and a far better system for your climate. See the
Aprilaire Dehumidifier.
Q. My preferred ventilation method is an
outside air duct to the central system return without any extra fan
cycling. Can I limit the outside air damper open time without having to
have fan cycling also?
A. To paraphrase, it seems that you want
central-fan-integrated supply ventilation only during normal calls for
cooling and heating, and you want to limit over-ventilation during
either long equipment runtimes (peak conditions or recovery from
setup/setback) or constant fan selection by the occupant. Both the
AirCycler® FR-V and the SCI ERV24 thermostat can be set to
cycle the motorized outside air damper to limit open time without
initiating any fan cycling. The FAN ON time would be set to zero, and
the VENT ON/DAMPER OPEN and VENT OFF/DAMPER CLOSED times would be set to
some limiting values that suited you. For example, you can set the
controls so that the damper would be open for a maximum of 20 minutes,
then be closed for at least 40 minutes.
Q. I have a 10,000 square foot house in
northern Illinois. We built it with 2x6 framing sheathed with 1” rigid
foam board, and all wall and ceiling cavities are sprayed full with
Icynene®. The basement walls have at least 6”of sprayed foam on the
interior, and we installed a full-height
insulation/drainage/waterproofing system on the exterior. The house has
been tested with a blower door and found to be exceptionally airtight.
There are five furnaces. I need a better way of being sure how much
ventilation air is needed. What are your thoughts?
A. Sounds like a great house! Here's my
advice on "enough ventilation." We think the house should be delivered
capable of meeting the ASHRAE 62.2-2003 Standard. That means that you
should have ventilation capacity capable of at least (7.5)(number of
bedrooms+1) + (0.01)(conditioned floor area). Given that the house has
10,000 ft2 floor area, and assuming it has five bedrooms, the
ventilation requirement would be (7.5)(6) + (0.01)(10,000) = 45 + 100 =
145 cfm. That 145 cfm would be the continuous rate, but you can do it
all with an intermittent system as long as you factor in the duty cycle
rate.
Having two 80 cfm, low sone bathroom exhaust fans with a standard wall
switch would meet the 62.2 Standard all by itself. Technically, the
switch for those fans should be marked "Ventilation." The occupants
could run them all of the time, part of the time, or none of the time,
and the Standard would still be met.
You might be thinking, how would two bathroom exhaust fans running
somewhere in a 10,000 square foot house provide any confidence of
ventilation air being distributed throughout the house? It doesn't. That
is why we believe the Standard should have requirements for ventilation
air distribution, which it may, someday. That is also why we always add
outside air to the central system return and use fan cycling to
distribute ventilation air and provide whole-house mixing -- smoothing
out differing air conditions throughout the house.
So what would I recommend for your house? Without having seen the plans,
I would add 50 cfm of outside air to at least 4 of the 5 air handlers,
via a 6" outside air duct to each, and set the individual fan cycling
controls to make sure the air handlers run 20 minutes per hour. I would
also make sure that enough bathroom exhaust fans, summing to 145 cfm,
were 1.0 sone or less to meet the 62.2 Standard.
Q. How do you test to know or estimate
how much outside air (OA) is coming into a home with a Central Fan
Integrated Supply (CFIS) ventilation system?
A. The most accurate way to measure OA
flow is the following:
- Turn the central system fan (the air handler) on, making sure that
any motorized damper in the outside air duct is open.
- Measure and record the operating pressure in the OA duct (using a
digital manometer/pressure gauge) upstream of any manual or motorized
dampers. This should be the intended pressure usually specified by the
ventilation system designer; if it is not at spec, adjust any manual
damper to increase or decrease air flow restriction until the intended
pressure is achieved or is as close as possible.
- Disconnect the OA duct where it connects to the return plenum.
- Connect the OA duct to a calibrated fan (Ductblaster™). Use the
ductblaster to take the OA duct back to the same pressure measured in
Step 2.
- Record the measured flow from the ductblaster.
While this level of testing accuracy can be laborious, after you have
performed enough tests of this nature to establish a good relationship
between duct pressure measurements and duct air flow, and you have
gained confidence over your range of systems and applications, you can
simply take pressure measurements and correlate them to air flow based
on the chart below and/or your own field experience.
|
|
Flow rate in outside air duct (cfm)
(with 25 ft of flex and 6" wall cap) |
|
OA duct pressure (Pa) |
OA
duct pressure (inch wc) |
Flex Duct Diameter (Inch) |
|
5 |
6 |
7 |
8 |
9
|
|
-5.0 |
-0.0201 |
32 |
37 |
53 |
63 |
66 |
|
-7.5 |
-0.0301 |
39 |
45 |
65 |
76 |
80 |
|
-10.0 |
-0.0402 |
45 |
52 |
75 |
87 |
91 |
|
-12.5 |
-0.0502 |
50 |
59 |
83 |
97 |
101 |
|
015.0 |
-0.0603 |
55 |
64 |
91 |
105 |
110 |
|
-17.5 |
-0.0703 |
59 |
69 |
99 |
113 |
119 |
|
-20.0 |
-0.0804 |
63 |
74 |
105 |
121 |
126 |
|
-22.5 |
-0.0904 |
67 |
79 |
112 |
127 |
133 |
|
-25.0 |
-0.1005 |
71 |
83 |
118 |
134 |
140 |
|
-27.5 |
-0.1105 |
74 |
87 |
123 |
140 |
146 |
|
-30.0 |
-0.1206 |
78 |
91 |
129 |
146 |
152 |
|
-35.0 |
-0.1407 |
84 |
98 |
139 |
157 |
164 |
|
-40.0 |
-0.1607 |
89 |
105 |
149 |
167 |
174 |
Note that these are all tests that an HVAC technician would perform.
FanCycler.com recommends a testing regimen similar to the one used by the EPA
Energy Star® program: test all of the first models of any product line, and then
test at least every 1 in 7 homes after that.
Q. We have
considered using central-fan-integrated supply (CFIS) ventilation to add fresh
air to the homes we build. We have heard about a duct mold problem with
ventilation into the central return, but that was with a different system. I am
wondering what risk there is for mold in the ducts using the CFIS system? My
location is in a mixed-humid climate.
A. By the fundamental principles, CFIS ventilation
cannot be a cause of mold in the ducts because the high percentage of
conditioned air from indoors (say 90%) mixed with the low percentage of outdoor
air (say 10%) eliminates that problem. We have never heard of mold in ducts
caused by CFIS ventilation after over 100,000 installations that we have been
connected with over the last ten years (1996 to 2006). These were in all U.S.
climates including mixed-humid.
My guess is that the system you heard about was injection of outside air into
the central return by a separate fan without the central fan running at the same
time. That is a mold disaster in any humid climate under cooling conditions.
Humid air contacts cool supply ducts and condenses after the cooling shuts off.
Q. A motorized
damper in an outside air duct that closes when the central air handler fan goes
off won’t allow make up air to enter, for instance, when the dryer or another
exhaust is on. Are there solutions to this?
A. Unless natural draft combustion appliances are
located inside the conditioned space (which they should not be), make-up air
should not be needed due to intermittent exhaust up to about 175 cfm. If you
still want the outside air duct to also serve as a passive make-up air duct then
here are two possible solutions:
- set the motorized damper for a minimum open position, that is,
set the damper stop (or install a bolt or screw) to stop the damper
from ever fully closing (say 50% minimum open); or
- eliminate the motorized damper, it may not be needed depending
on the maximum ventilation air flow desired and wind shielding of
the outside air inlet
|